Isolation Switching Amplifier for Pulse Generators REL-7
| Product Specifications | |
|---|---|
| For transmission of pulse signals | |
| Protection | EEx ia IIC |
| Input | intrinsicly safe, up to 5 kHz |
| output | non intrinsicly safe, |
| 1-Signal | |
| Electronic output active | |
| 2-line interruption, | |
| Electronic output active | |
| Power supply | 20..30 VDC |
| Mounting | rail mounting |
The isolation switching amplifier transmits pulse signals of up to 5 kHz from hazardous areas. Sensors according to NAMUR or mechanical contacts may be used as signal transmitters. The control circuit is monitored for line interruption (LB) and line short-circuit (LK). The input is safely isolated from the output and mains according to DIN EN 50 020. The devices are fitted with detachable terminals that greatly simplify installation.